York R-407C Air Conditioner User Manual


 
YORK INTERNATIONAL
26
TABLE 7 – COOLING PERFORMANCE DATA* – 75 TON MODEL
Cooling Performance Data – 75 Ton Model
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
35°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
29.4°C AIR ON CONDENSER COIL
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 244 183 233 159 233 141 232 123 230 104
27184 19 228 210 217 191 216 174 216 155 215 137 214 119
17 228 219 215 214 202 201 202 184 200 170 199 151
22 255 211 243 181 242 158 241 136 240 112
33980 19 244 237 231 220 227 198 226 174 224 153 223 131
17 248 238 234 237 217 224 216 209 211 193 209 170
22 259 224 247 191 245 166 244 141 243 116
37378 19 252 246 238 234 230 209 229 184 228 160 226 136
17 255 245 242 245 223 229 224 220 215 205 212 179
22 259 226 247 193 246 168 245 142 243 117
38228 19 254 247 239 237 231 212 230 186 228 161 227 136
17 256 246 243 246 224 230 225 222 216 207 213 180
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 235 183 233 159 233 141 232 123 230 104
27184 19 220 210 217 191 216 174 216 155 215 137 214 119
17 224 219 215 214 202 201 202 184 200 170 199 151
22 246 211 243 181 242 158 241 136 240 112
33980 19 236 237 231 220 227 198 226 174 224 153 223 131
17 243 238 234 237 217 224 216 209 211 193 209 170
22 250 224 247 191 245 166 244 141 243 116
37378 19 244 246 238 234 230 209 229 184 228 160 226 136
17 250 245 242 245 223 229 224 220 215 205 212 179
22 250 226 247 193 246 168 245 142 243 117
38228 19 245 247 239 237 231 212 230 186 228 161 227 136
17 251 246 243 246 224 230 225 222 216 207 213 180