York R-407C Air Conditioner User Manual


 
FORM 100.50-EG3 (802)
33
YORK INTERNATIONAL
TABLE 10 – COOLING PERFORMANCE DATA* – 90 TON MODEL (CONT’D)
46.1°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
40.5°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 288 227 286 197 285 174 284 152 282 129
33980 19 273 262 266 238 265 215 264 191 263 169 261 147
17 274 274 269 270 262 263 247 228 243 209 243 186
22 299 254 297 218 295 191 294 165 292 138
40776 19 291 295 278 267 276 239 275 210 273 184 271 158
17 296 296 288 291 280 288 261 257 254 232 253 204
22 305 272 302 231 301 201 299 172 297 143
45307 19 304 314 284 285 282 254 280 222 278 193 276 165
17 309 309 296 300 294 302 269 275 259 247 258 215
22 310 285 306 241 304 209 303 178 300 147
50970 19 314 328 289 298 286 265 284 231 282 201 280 170
17 319 319 303 307 304 312 276 288 264 258 262 223
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 276 223 274 192 273 170 272 148 270 125
33980 19 260 256 255 233 254 210 253 186 252 164 250 143
17 261 261 259 259 253 253 237 223 233 204 232 181
22 287 249 285 212 283 186 282 159 280 133
40776 19 277 287 267 260 265 233 263 204 261 179 260 153
17 282 282 276 279 271 278 250 252 243 226 242 198
22 293 266 290 225 288 196 287 167 284 138
45307 19 289 302 272 278 270 248 268 216 266 188 265 159
17 294 294 284 288 284 292 258 267 248 240 247 208
22 297 279 294 235 292 203 290 172 288 143
50970 19 299 312 277 291 274 260 272 225 270 195 268 164
17 304 304 291 295 293 302 264 276 252 251 251 216