York R-407C Air Conditioner User Manual


 
FORM 100.50-EG3 (802)
35
YORK INTERNATIONAL
TABLE 11 – COOLING PERFORMANCE DATA* – 95 TON MODEL (CONT’D)
46.1°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
40.5°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 305 247 304 214 303 189 301 164 300 137
33980 19 288 285 282 258 282 233 281 207 279 183 277 152
17 293 293 285 288 272 277 262 248 259 227 258 196
22 308 249 307 216 305 191 304 165 302 138
40776 19 290 288 285 260 285 236 284 209 282 185 280 154
17 297 297 289 292 275 281 266 251 263 230 261 198
22 309 250 308 217 307 192 305 166 303 139
45307 19 292 289 287 262 286 237 285 210 284 186 282 155
17 300 300 291 295 278 283 268 254 265 232 264 200
22 310 251 309 218 308 192 306 166 304 139
50970 19 293 291 288 263 288 238 287 211 285 187 283 155
17 302 302 294 297 280 286 271 256 267 234 266 202
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 293 241 291 209 290 184 289 159 287 132
33980 19 275 279 271 252 270 227 269 202 267 177 266 147
17 280 280 275 278 264 272 251 242 248 221 247 190
22 296 243 294 211 292 185 291 160 289 133
40776 19 278 282 274 255 273 230 272 204 270 179 268 149
17 284 284 279 282 268 275 254 245 252 224 250 193
22 297 244 295 212 294 186 292 161 291 134
45307 19 280 283 275 256 274 231 273 205 272 180 270 150
17 287 287 281 285 271 278 257 248 254 226 253 195
22 298 244 296 213 295 187 293 162 292 134
50970 19 281 285 277 257 275 232 275 206 273 181 271 150
17 289 289 284 287 273 280 259 249 256 228 254 196