York R-407C Air Conditioner User Manual


 
YORK INTERNATIONAL
18
TABLE 3 – COOLING PERFORMANCE DATA* – 55 TON MODEL
Cooling Performance Data – 55 Ton Model
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
35°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
29.4°C AIR ON CONDENSER COIL
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 197 148 197 130 196 116 195 103 194 89
20388 19 185 167 181 153 181 139 182 125 180 113 178 100
17 183 183 175 178 166 171 167 147 166 136 166 123
22 202 159 201 138 201 123 200 107 198 92
27184 19 192 186 186 166 186 150 186 134 185 119 183 104
17 193 193 185 187 177 174 173 159 171 146 171 131
22 209 175 207 150 207 132 206 113 204 96
32706 19 202 211 193 183 193 164 192 145 192 127 190 109
17 206 206 197 199 190 195 180 176 178 159 177 141
22 210 177 208 151 208 133 206 114 205 96
33980 19 204 213 194 185 193 166 193 147 193 128 191 110
17 208 208 199 201 192 197 181 178 179 161 178 143
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 190 145 190 126 189 113 189 100 187 87
20388 19 178 162 175 150 175 136 175 122 174 113 173 97
17 178 178 171 173 163 167 162 145 161 133 160 119
22 195 156 194 135 193 120 193 107 192 89
27184 19 186 182 180 162 179 147 179 131 178 113 177 101
17 188 188 180 182 172 170 167 156 165 143 165 128
22 201 171 200 148 199 129 198 129 197 92
32706 19 197 205 187 178 186 162 185 143 184 122 183 106
17 200 200 192 194 184 189 173 171 171 157 171 140
22 202 173 201 149 200 130 199 132 198 92
33980 19 198 207 187 180 187 164 186 144 185 123 184 107
17 202 202 193 196 185 190 174 173 172 158 172 142