York R-407C Air Conditioner User Manual


 
FORM 100.50-EG3 (802)
27
YORK INTERNATIONAL
TABLE 7 – COOLING PERFORMANCE DATA* – 75 TON MODEL (CONT’D)
46.1°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
40.5°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 226 183 233 159 233 141 232 123 230 104
22718484271 19 219 210 217 191 216 174 216 155 215 137 214 119
17 219 219 215 214 202 201 202 184 200 170 199 151
22 236 211 243 181 242 158 241 136 240 112
33980 19 235 237 231 220 227 198 226 174 224 153 223 131
17 238 238 234 237 217 224 216 209 211 193 209 170
22 240 224 247 191 245 166 244 141 243 116
37378 19 243 246 238 234 230 209 229 184 228 160 226 136
17 245 245 242 245 223 229 224 220 215 205 212 179
22 241 226 247 193 246 168 245 142 243 117
38228 19 244 247 239 237 231 212 230 186 228 161 227 136
17 246 246 243 246 224 230 225 222 216 207 213 180
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 217 183 233 159 233 141 232 123 230 104
27184 19 212 210 217 191 216 174 216 155 215 137 214 119
17 212 219 215 214 202 201 202 184 200 170 199 151
22 227 211 243 181 242 158 241 136 240 112
33980 19 227 237 231 220 227 198 226 174 224 153 223 131
17 230 238 234 237 217 224 216 209 211 193 209 170
22 231 224 247 191 245 166 244 141 243 116
37378 19 235 246 238 234 230 209 229 184 228 160 226 136
17 237 245 242 245 223 229 224 220 215 205 212 179
22 231 226 247 193 246 168 245 142 243 117
38228 19 236 247 239 237 231 212 230 186 228 161 227 136
17 238 246 243 246 224 230 225 222 216 207 213 180