TABLE 5 – COOLING PERFORMANCE DATA* – 65 TON MODEL
Cooling Performance Data – 65 Ton Model
29.4°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
35°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 226 172 226 150 225 134 224 118 223 102
23786 19 215 196 209 179 208 162 208 146 207 130 206 114
17 211 211 202 205 193 186 194 172 192 159 192 143
22 235 193 233 166 232 147 231 127 230 108
30582 19 225 226 217 201 217 182 216 161 215 142 214 122
17 227 227 218 220 209 210 202 193 200 176 199 157
22 240 206 238 177 237 155 236 133 234 111
35679 19 234 244 223 216 222 194 221 171 220 149 218 128
17 238 238 227 224 219 215 208 196 205 177 204 155
22 241 210 239 180 238 157 237 134 236 112
38228 19 236 246 224 219 223 197 222 173 221 151 220 129
17 240 240 230 213 222 194 209 173 206 154 205 132
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 218 168 217 147 217 131 216 115 214 99
23786 19 210 193 201 175 201 159 201 142 200 127 199 111
17 205 205 197 199 188 182 187 169 185 156 184 139
22 226 189 224 163 224 143 223 123 221 104
30582 19 218 220 209 197 209 178 208 157 207 138 206 119
17 221 221 211 214 203 204 195 189 193 173 192 154
22 231 203 229 173 228 151 227 129 225 108
35679 19 227 237 214 212 214 190 212 167 211 146 210 124
17 231 231 220 221 212 217 200 202 197 184 196 162
22 232 206 230 176 229 153 228 131 226 109
38228 19 229 239 216 215 215 193 214 170 212 148 211 125
17 233 233 221 218 215 216 201 203 199 185 198 162