York R-407C Air Conditioner User Manual


 
FORM 100.50-EG3 (802)
17
YORK INTERNATIONAL
TABLE 2 – COOLING PERFORMANCE DATA* – 50 TON MODEL (CONT’D)
46.1°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
40.5°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 175 136 175 119 174 105 173 93 173 80
22653 19 164 154 162 142 160 128 160 114 160 102 159 90
17 168 168 161 163 150 147 150 135 148 126 147 111
22 176 138 176 120 174 106 174 94 173 81
25485 19 165 156 163 144 161 130 161 115 161 103 160 90
17 169 169 162 164 152 149 151 137 149 127 148 113
22 177 140 176 122 175 108 175 95 174 81
29733 19 167 160 164 146 162 132 162 117 162 104 161 91
17 171 171 164 166 154 152 152 140 150 129 149 114
22 181 149 180 129 179 113 178 98 177 83
31148 19 175 177 169 157 167 141 166 125 165 109 164 94
17 179 179 171 173 163 164 155 151 153 137 152 120
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 168 133 167 115 165 101 164 90 163 78
22653 19 159 153 155 138 154 126 152 112 151 99 151 87
17 161 161 154 156 145 147 142 132 140 123 139 109
22 169 135 168 116 166 102 165 90 164 78
25485 19 160 156 156 140 154 127 153 113 152 100 151 87
17 163 163 155 157 147 149 143 135 140 124 139 110
22 170 137 169 118 167 104 166 91 165 79
29733 19 162 158 157 142 155 129 154 114 153 101 152 88
17 165 165 157 158 149 151 144 138 142 126 140 111
22 174 147 172 125 171 109 170 95 169 80
31148 19 169 172 160 151 160 137 159 121 158 106 156 91
17 172 172 163 165 157 160 150 150 146 134 145 118