York R-407C Air Conditioner User Manual


 
FORM 100.50-EG3 (802)
31
YORK INTERNATIONAL
TABLE 9 – COOLING PERFORMANCE DATA* – 85 TON MODEL
46.1°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
40.5°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 257 196 256 172 255 153 254 133 252 114
27184 19 241 223 237 204 236 185 236 166 234 148 233 129
17 239 239 233 225 232 223 219 196 217 181 216 162
22 264 209 263 181 262 161 261 140 259 118
30582 19 248 239 244 217 242 196 242 175 241 155 240 135
17 249 249 244 242 239 238 226 209 223 192 222 170
22 275 233 273 199 272 175 270 151 268 126
37378 19 264 269 254 242 253 218 252 192 250 168 249 144
17 269 269 261 264 256 263 240 237 233 212 231 186
22 284 258 281 218 280 190 278 161 276 134
45307 19 286 299 263 268 262 241 260 210 258 182 257 154
17 291 291 272 276 279 287 256 268 242 234 239 203
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 246 191 246 168 245 149 244 129 242 110
27184 19 231 219 227 199 226 181 226 162 225 144 224 124
17 230 230 224 217 224 216 210 191 208 177 207 157
22 253 204 252 177 251 156 250 135 248 114
30582 19 238 234 234 212 232 192 232 171 231 151 230 130
17 240 240 235 233 231 230 216 204 214 187 213 165
22 263 227 262 195 261 170 259 146 257 122
37378 19 254 263 244 237 242 212 242 187 240 164 239 140
17 258 258 251 254 247 254 230 231 223 206 222 181
22 272 252 270 213 269 185 267 156 264 130
45307 19 275 287 252 263 251 235 249 204 247 176 246 149
17 280 280 262 265 270 277 245 256 232 228 229 197