TABLE 11 – COOLING PERFORMANCE DATA* – 95 TON MODEL
Cooling Performance Data – 95 Ton Model
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
35°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
29.4°C AIR ON CONDENSER COIL
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 324 250 323 222 322 197 321 171 319 143
33980 19 304 293 298 265 298 241 299 215 297 191 295 159
17 310 310 298 302 282 272 278 256 275 235 274 203
22 337 271 335 239 334 210 332 182 330 152
40776 19 324 317 311 287 311 259 310 231 308 204 306 169
17 330 330 313 317 299 292 293 280 287 254 285 218
22 343 289 341 253 339 221 338 190 336 158
45307 19 339 341 318 306 317 276 316 244 314 214 312 176
17 344 344 323 327 313 313 303 301 293 270 291 230
22 349 303 346 264 344 230 342 196 340 163
50970 19 349 360 323 321 322 289 320 254 319 222 316 181
17 355 355 330 334 324 330 310 317 298 282 295 238
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 312 250 312 217 311 192 309 166 307 139
33980 19 293 288 289 261 288 236 288 210 286 186 284 155
17 298 298 290 293 274 278 268 251 265 230 264 199
22 325 271 323 234 322 205 320 177 318 148
40776 19 313 312 301 282 300 254 299 225 297 199 295 164
17 318 318 304 308 290 293 283 274 277 248 275 213
22 332 289 329 248 327 216 326 185 324 153
45307 19 326 335 308 301 306 271 305 238 303 209 301 171
17 332 332 314 317 304 310 292 295 283 263 280 225
22 337 303 333 259 332 224 330 191 328 158
50970 19 337 352 313 316 311 283 309 248 307 216 305 176
17 342 342 321 325 315 324 299 311 287 275 285 233