TABLE 10 – COOLING PERFORMANCE DATA* – 90 TON MODEL
Cooling Performance Data – 90 Ton Model
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
35°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
29.4°C AIR ON CONDENSER COIL
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 310 233 308 206 307 183 306 161 304 137
33980 19 292 272 286 247 286 224 285 200 283 179 282 156
17 293 293 286 286 269 258 266 239 262 219 262 195
22 322 260 320 228 318 201 317 174 315 146
40776 19 311 307 298 277 297 249 296 220 294 195 293 168
17 317 317 305 308 289 287 281 269 274 243 272 214
22 329 278 325 242 324 211 322 182 320 152
45307 19 325 328 305 295 304 265 301 233 300 205 298 175
17 330 330 314 318 302 305 290 290 280 258 278 225
22 334 292 330 252 328 219 326 188 324 157
50970 19 335 345 310 310 308 277 306 242 304 212 302 180
17 341 341 321 325 313 319 297 305 284 269 282 234
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 299 233 298 202 296 179 295 157 293 133
33980 19 281 268 277 243 276 220 275 196 273 174 272 152
17 282 282 277 278 262 263 257 234 253 214 252 191
22 311 260 309 223 307 196 306 169 303 142
40776 19 300 302 288 272 287 244 285 215 284 189 282 163
17 305 305 296 300 280 288 271 264 264 237 263 209
22 317 278 314 237 313 206 311 177 309 148
45307 19 313 322 295 291 293 260 291 227 289 199 287 169
17 318 318 305 309 294 302 280 284 270 252 268 220
22 322 292 318 247 317 214 315 183 313 152
50970 19 323 337 300 305 298 272 295 236 293 206 291 175
17 329 329 312 316 304 313 287 299 274 263 272 229