York R-407C Air Conditioner User Manual


 
YORK INTERNATIONAL
16
Cooling Performance Data – 50 Ton Model
TABLE 2 – COOLING PERFORMANCE DATA* – 50 TON MODEL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
35°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
29.4°C AIR ON CONDENSER COIL
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 189 141 188 125 187 111 186 99 186 86
22653 19 179 162 175 148 173 134 173 121 171 108 170 96
17 179 179 170 172 164 169 160 156 156 143 157 125
22 190 143 189 126 188 112 187 100 187 86
25485 19 180 165 175 150 173 135 173 122 172 109 171 97
17 180 180 172 174 166 168 161 153 157 140 158 122
22 191 146 190 128 189 113 188 101 187 87
29733 19 181 168 176 152 175 138 174 124 173 110 172 97
17 181 181 173 176 167 164 162 150 158 137 159 119
22 196 156 193 134 193 119 192 104 191 89
31148 19 186 184 181 163 180 147 179 130 178 115 176 100
17 189 189 181 183 175 179 167 158 165 144 164 126
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 182 138 181 121 180 108 180 96 179 83
22653 19 173 159 170 146 167 131 167 118 165 107 164 93
17 173 173 166 167 159 150 156 140 153 128 153 114
22 183 140 182 123 181 109 180 97 180 84
25485 19 174 162 171 148 168 133 168 119 166 107 165 94
17 175 175 167 169 160 152 157 142 154 130 154 115
22 184 143 183 124 182 110 181 97 180 84
29733 19 175 165 171 150 169 135 169 120 167 107 166 94
17 177 177 169 171 162 155 158 144 155 132 155 117
22 188 153 187 132 186 116 185 101 184 87
31148 19 182 182 175 159 174 144 173 128 171 109 170 97
17 184 184 176 178 169 169 162 153 159 140 159 125