York R-407C Air Conditioner User Manual


 
YORK INTERNATIONAL
30
Cooling Performance Data – 85 Ton Model
TABLE 9 – COOLING PERFORMANCE DATA* – 85 TON MODEL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
35°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
29.4°C AIR ON CONDENSER COIL
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 277 204 277 180 275 160 274 141 273 121
27184 19 260 232 255 213 255 194 255 175 253 156 252 137
17 258 258 247 239 239 220 236 204 234 190 233 171
22 285 217 284 190 282 169 281 148 279 125
30582 19 267 249 263 227 262 206 262 184 260 164 259 143
17 269 269 260 257 246 235 244 218 241 201 240 180
22 296 242 294 209 293 184 292 159 290 134
37378 19 285 280 274 253 273 228 272 202 271 178 269 153
17 290 290 277 281 264 262 258 247 252 222 250 196
22 306 269 303 229 302 200 300 170 298 142
45307 19 309 315 284 281 283 252 281 221 279 192 277 164
17 314 314 289 293 287 292 276 283 261 245 258 214
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 267 200 267 176 266 157 264 137 263 117 ––
27184 19 250 229 246 209 246 190 245 171 244 152 243 133
17 249 249 240 232 232 224 228 201 225 185 225 166
22 275 213 273 186 272 165 271 144 269 122 ––
30582 19 257 245 254 222 253 202 252 180 251 160 249 139
17 259 259 252 250 239 238 235 214 232 196 231 175
22 286 237 284 204 283 180 281 155 279 130 ––
37378 19 275 276 265 248 263 223 262 197 261 173 259 149
17 279 279 269 272 256 263 249 243 242 216 241 191
22 295 264 292 224 291 195 289 166 287 138 ––
45307 19 297 310 274 275 273 247 270 215 269 187 267 159
17 302 302 281 284 279 287 267 278 251 238 249 208