Trane SCWG 020, SCWG 025, SCWG 030, SCWG 035, SIWG 020, SIWG 025, SIWG 030, SIWG 035, SCRG 020, SCRG 025, SCRG 032, SIRG 020, SIRG 025, SIRG 032 Heating System User Manual


 
SCXG-SVX01B-EN 99
Supply Fan
Fan Drive
Perform the following procedures
according to the Periodic Maintenance
Check List on page 110.
Disconnect electrical power
source to prevent injury or death
from electrical shock.
1. Rotate the fan wheel to be sure it turns
freely in the proper direction and is not
rubbing on the fan housing, inlet, or inlet
guide vanes. If necessary, center the
fan wheel again.
2. Check the position of both shafts. Fan
and motor shafts should operate
parallel to each other for maximum belt
and bearing life. Shim as necessary
under the motor or fan bearings to
obtain proper alignment.
3. Check the fan motor sheave alignment
with straight edge or a tightly pulled
string. For sheaves of different widths,
place a string in the center groove of
!
WARNING
each sheave and pull it tight for a center
line. See Figure O-M-2 on page 100 for
recommended torques.
4. Once the sheaves are properly aligned,
tighten sheave set screws to proper
torque.
5. Check belt tension. Refer to the
Measuring Belt Tension section on
page 100.
6. If required, adjust belt to the minimum
recommended tension. Refer to
Adjusting Belt Tension section on
page 100.
7. Retighten bearing set screws to the
proper torques after aligning the
sheaves.
8. Check the fan bearing locking collars
for tightness on the shaft. To tighten the
locking collar, loosen the set screw and
slide the collar into its proper position
over the extended end of the inner
case. Tighten the set screw to the
appropriate torque value.
9. During air balancing, verify the sheave
alignment, belt tension, and that the
shaft is parallel.
Figure O-M-1. Fan shaft and motor sheave alignment.
Owner
Maintenance