Trane SCWG 020, SCWG 025, SCWG 030, SCWG 035, SIWG 020, SIWG 025, SIWG 030, SIWG 035, SCRG 020, SCRG 025, SCRG 032, SIRG 020, SIRG 025, SIRG 032 Heating System User Manual


 
12 SCXG-SVX01B-EN
Figure I-PC-6. Split-apart unit gravity block location.
Figure I-PC-5. Assembled unit gravity block location.
Table I-PC-2. Gravity Block Dimensions
Model A B C D
SXWG 36 14 38 12
SXRG 36 16 40 12
Rigging and Unit Handling
Before lifting the unit or modular
component, determine the approximate
center of gravity for lifting safety. See
Figure I-PC-5 for assembled modular
units and Figure I -PC-6 for split-apart
units. The center of gravity may vary
slightly within the gravity block
depending on unit options.
Ensure lifting equipment capacity
exceeds unit weight by an
adequate safety factor to prevent
injury, death, or unit damage.
Always test-lift the unit to determine the
exact unit balance and stability before
hoisting it to the installation location. See
Figures I-PC-7 and I-PC-8 for typical
rigging procedures and proper rigging
equipment usage.
To prevent injury or death and
unit damage, always test-lift the
unit to determine actual center of
gravity.
See Figures I-PC-5 and I-
PC-6.
Pre-Installation
Considerations
Installation
WARNING
!
ƽƽ
ƽƽ
ƽ
WARNING
!
Fan Section Only
Compressor Section Only