Trane SCWG 020, SCWG 025, SCWG 030, SCWG 035, SIWG 020, SIWG 025, SIWG 030, SIWG 035, SCRG 020, SCRG 025, SCRG 032, SIRG 020, SIRG 025, SIRG 032 Heating System User Manual


 
SCXG-SVX01B-EN 83
Table O-GI-6. GBAS Analog Input Setpoints
Control Parameter Signal Range Setpoint Range
Occupied Zone Cooling Setpoint 0.5 to 4.5 vdc 50 to 90 F
(CV units only)
Unoccupied Zone Cooling Setpoint 0.5 to 4.5 vdc 50 to 90 F
(CV and VAV)
Occupied Zone Heating Setpoint 0.5 to 4.5 vdc 50 to 90 F
(CV units only)
Unoccupied Zone Heating Setpoint 0.5 to 4.5 vdc 50 to 90 F
(CV and VAV)
Supply Air Cooling Setpoint 0.5 to 4.5 vdc 40 to 90 F
(VAV units only)
Supply Air Hydronic Heating Setpoint 0.5 to 4.5 vdc 40 to 180 F
(VAV units only)
Space Static Pressure Setpoint 0.5 to 4.5 vdc 0.03 to 0.30 IWC
Supply Air Pressure Setpoint 0.5 to 4.5 vdc 0.0 to 5.0 IWC
(VAV units only)
Note: 1. Input voltages less than 0.5 vdc are considered as 0.5 vdc input signal is lost, the setpoint will
clamp to the low end of the setpoint scale. No diagnostic will result from this condition.
2. Input voltages greater than 4.5 vdc are considered to be 4.5 vdc.
3. The actual measured voltage is displayed at the HI.
Table O-GI-7. GBAS Input Voltage Corresponding Setpoints
Volts Temp. Volts Temp. Volts Temp Volts Temp
(F) (F) (F) (F)
0.5 50 1.6 60 2.6 70 2.7 80
0.6 51 1.7 61 2.7 71 2.8 81
0.7 52 1.8 62 2.8 72 2.9 82
0.8 53 1.9 63 2.9 73 3.0 83
0.9 54 2.0 64 3.0 74 3.1 84
1.0 55 2.1 65 3.1 75 3.2 85
1.1 56 2.2 66 3.2 76 3.3 86
1.2 57 2.3 67 3.3 77 3.4 87
1.3 58 2.4 68 3.4 78 3.5 88
1.5 59 2.5 69 3.5 79 3.6 89
Owner
General
Information