Quadra-Fire 7046-137C Indoor Fireplace User Manual


 
Page 28
7046-137C
December 15, 2009
R
2700-I ACC Wood Insert
10 ft. (305cm) or more
3 ft. (91cm) Minimum
Less than 10 ft. (305cm)
2 ft. (61cm)Minimum
3 ft. (91cm) Minimum
Wall or Parapet
Flat Roof
 ft. (91cm)
Minimum
Less than 10 ft. (05cm)
2 ft. (61cm)
 ft. (91cm)
Minimum
10 ft. (05cm) To Nearest Roofline
2 ft. (61cm)
Pitched Roof
These are safety requirements and are not meant to assure proper ue draft.
Figure 28.1
F. 2-10-3 Rule
Figure 28.2
This appliance is made with a 6 inch (152mm) diameter chimney connector as the ue collar on the unit.
Changing the diameter of the chimney can affect draft and cause poor performance.
It is not recommended to use offsets and elbows at altitudes above 4000 feet above sea level and or when
there are other factors that affect ue draft.