Crestron electronic CHV-TSTATRF Thermostat User Manual


 
Crestron CHV-TSTATRF infiNET™ Thermostat
it will display “—” when a function is selected. All other display elements will be
hidden (refer to “LCD Display” on page 25).
NOTE: While in Setup mode, a period of one minute with no button activity will
cause the CHV-TSTATRF to revert to standard operation, unless a function (such as
an infiNET acquire) is executing.
Setup Mode Parameters/Functions
The following table shows the available setup parameters/functions.
Setup Mode Parameters/Functions
PARAMETER/
FUNCTION
CODE VALID VALUES
DEFAUL
T VALUE
NOTES
Temperature Scale FC F, C1 or C2 F
Sets units to use for temperature
display
(Fahrenheit or Celsius).
When using Celsius temperature
scale, C2 allows the setpoint to
be adjusted in 0.5ºC steps.
Backlight Timeout bL
1 – 4 seconds or
disabled (--)
--
Sets the number of seconds the
backlight will remain lit after a
button press.
Heat/Cool Type HC
Heat/Cool (HC), Heat
pump (HP), Dual-Fuel
Heat pump (dF)
HC
Sets the system type being used.
Heat pump type will allow aux
heat to stage with the heat pump.
A dual-fuel heat pump type will
not allow both systems to run at
the same time.
Temperature Offset to
-9 to +9 (for Fahrenheit)
or
-5 to +5 (for Celsius)
0
Permits recalibration of room
temperature sensor. This is the
number of degrees added to or
subtracted from the actual
temperature. This adjustment
changes the actual regulation
temperature, not just the display.
Wide-range Cool Mode
(Extended Cool)
EC
Enabled (Y) or Disabled
(no)
no
Useful for wine chiller
applications; extends the cool
setpoint range down to the
minimum used for Heat mode
(38ºF/3ºC).
Heat Anticipator HA 1 – 6 3
Lower setting results in more
frequent cycles and faster
response (tighter regulation).
Higher setting results in less
frequent cycles and slower
response (looser regulation). The
default value should suffice in
nearly all installations.
(Continued on following page)
Operations & Installation Guide – DOC. 6490 infiNET™ Thermostat: CHV-TSTATRF 19