Conair Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control Air Conditioner User Manual


 
CONTROL
SETTINGS
UGH016/0601 Series 1 Portable Chillers, TIC Control
APPENDIX D-1
Display
InP
DSPL
OutP
Cnrl
Parameter
SP.LL
SP.HL
TyPE
dspl
Unit
O1.ty
O1.ac
O1.cy
O1.hl
O2.ty
O2.aa
O2.ao
O2.ih
O2.SP
Pb1
der
OFFS
Int
Description
Lower Setpoint limit
Upper Setpoint Limit
Input sensor type
Display menu
Temperature units
Output 1 Type
Output 1 action
Output 1 cycle type
Output 1 High limit
Output 2 Control Type
Output 2 Alarm 1 Action
Output 2 process
Output 2 alarm inhibit
Output 2 alarm setpoint
Proportional Band-gain
Derivative Action - rate
Manual reset
Integral Action - reset
Setting
40
70
rtd
----
F
PID
re
5
80%
ALr
nor
DE.L
En
4
1
0
OFF
0
Units
°F
°F
100 ohm rtd
-----
°F or °C
-----
Reverse action
Seconds
% time HGV is on
-----
-----
Alarm set to low deviation
Enabled
°F Low deviation
-----
-----
-----
-----
Use this table when configuring the temperature controller.
Refer to the manufacturer’s manual that accompanies this
User Guide for detailed information.
When the control displays the text listed in the Display col-
umn, you can scroll to, and change, the settings listed in the
Parameter column.