Conair Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control Air Conditioner User Manual


 
MECHANICAL
CONDITIONS
Series 1 Portable Chillers, TIC Control UGH016/0500
6-8
TROUBLESHOOTING
Alarm
Flow fault (pump
and compressor are
off)
Possible cause
The To Process and From
Process valves are closed.
The Process Fluid strain-
er is clogged.
Water level in reservoir is
low.
The evaporator is fouled.
Pump is not running.
Pump is running back-
wards.
Solution
Open valve(s).
Clean the strainer.
Fill the reservoir. See Making
Process Plumbing
Connections, in the Installation
section.
Clean Evaporator. See
Cleaning the Evaporator or
Water-cooled Condenser, in the
Maintenance section.
Check overload module.
Replace as needed. See
Replacing Overload Modules,
in the Troubleshooting section.
Switch any two of the three
main power leads to the pump.