TROUBLESHOOTING 6-21
R
EMOVING
PUMP
COMPONENTS
The pump’s wet end (impeller, motor, and seal assembly) can
be removed for service.
Disconnect and lockout power to the chiller.
Open the drain/fill valve.
Drain the water from the chiller.
1
2
Fill/Drain valve
Open the side of the chiller.
Remove the bolts connecting the pump
assembly to the pump housing.
Remove the pump assembly.
Carefully slide it sideways away from the pump tank to
avoid damage.
Inspect, clean, and replace pump parts
as needed. Separate the pump assembly form the pump
volute (casing) by prying the flanges and pulling apart.
Follow the disassembly and reassembly procedures in the
pump manufacturer’s manual that accompanies this User
Guide.
3
4
5
6
Open
this
side