Conair Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control Air Conditioner User Manual


 
P
REPARING FOR
INSTALLATION
Series 1 Portable Chillers, TIC Control UGH016/0500
3-4
INSTALLATION
Plan the location for the chiller and prepare the area properly.
Position the Chiller as close to the process machine as possi-
ble. Place the chiller in position near the process machine so
that fluid lines can be connected from the process machine to
the chiller and back.
Make sure the area where the chiller is installed has:
A grounded power source.
Check the chiller’s serial tag for the correct amps, volt-
age, phase, and cycle. All wiring should be completed by
qualified personnel and comply with your region’s elec-
trical codes.
Clearance for safe operation and maintenance.
Make sure there is two feet clearance around the chiller
for proper operation, maintenance, and servicing. After
positioning, lock casters to prevent chiller from moving.
Available water source.
If installing a water-cooled unit, makes sure water source
is plumbed to chiller installation location. High points in
plumbing require vent valves; low points require drain
valves.
Chiller
Process machine
Alternate
locations
24 inches
(610 mm)
24 inches
(610 mm)
24 inches
(610 mm)
24 inches
(610 mm)