Conair Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control Air Conditioner User Manual


 
Check the fluid level in the reservoir. The meniscus in the
sight glass on the back of the chiller should be in line with the
mark on the sight glass.
To manually fill the reservoir:
Disconnect and lockout power to the chiller.
Locate the fill port on the back of the chiller.
Refill the reservoir.
Monitor the level using the water level gauge on the back
of the chiller. Because the Portable Chiller can use either
pure water or a glycol solution, make sure your are
adding the correct fluid for your application.
C
HECKING
RESERVOIR
LEVEL
Series 1 Portable Chillers, TIC Control UGH016/0500
5-10
MAINTENANCE
If you have the optional make-up water level float switch, it
will automatically control the fluid level.
WARNING: Electrical hazard
Before performing any work on this item, dis-
connect and lock out electrical power sources to
prevent injury from unexpected energization or
startup.
1
2
3
Fill/Drain valve
Water level gauge
Fill port