Carrier JK034-074 Air Conditioner User Manual


 
LEGEND AND NOTES FOR FIG. 55
ALM Alarm
C—Contactor
CB Circuit Breaker
CCB Control Circuit Breaker
COMP Compressor
CH Crankcase Heater
CR Control Relay
DPS Differential Pressure Switch
DPT Discharge Pressure Transducer
EAT Enering-Air Temperature
EC Enthalpy Control
ECR Economizer Close Relay
EOR Economizer Open Relay
EQUIP Equipment
FS Fan Status Switch
GND Ground
HIR Heat Interlock Relay
HPS High-Pressure Switch
HR Heater Relay
HTR Heater
IDC Induced Draft Contactor
IDM Induced Draft Motor
IFC Indoor (Evaporator) Fan Contactor
IFCB Indoor Fan Circuit Breaker
IGV Inlet Guide Vanes
IGVM Inlet Guide Vanes Motor
LAT Leaving-Air Temperature
LPS Low-Pressure Switch
MTR Motor
MV Main Valve
NC Normally Closed
NO Normally Open
OFC Outdoor Fan Contactor
OFM Outdoor (Condenser) Fan Motor
OMR Outdoor Motor Relay
PCB Power Exhaust Circuit Breaker
PEC Power Exhaust Contactor
PEDM Power Exhaust Damper Motor
PEM Power Exhaust Motor
P, PL Plug
RCB Return Fan Circuit Breaker
RES Resistor
RFC Return Fan Contactror
RFM Return Fan Motor
SCT Saturated Condensing Thermistor
TB Terminal Block
TRAN Transformer
U—Unloader
VFD Variable Frequence Drive
Field Wiring
Factory Wiring
NOTES:
1. Connect TRAN1 to
H4
for 460 v units. Connect to
H3
for 230 v
units. If 208/230 v units are run with a 208 v power supply
connect to
H2
.
2. ConnectTRAN2 to BLKlead for460 vunits. Connectto ORNlead
for 230 v units. If 208/230 v units are run with a 208 v power sup-
ply connect to RED lead.
3. Circuitbreaker must tripamps areequal to orless than 156%FLA
(full load amps) for CB1 and CB2. All others are 140%.
4. If any of the original wire furnished must be replaced, it must be
replaced with type 90° C wire or its equivalent.
5. Number(s) indicates the line location of contacts. A bracket over
(2) numbers signifies single pole double throw contacts. An un-
derlined number signifies a normally closed contact. Plain num-
bers (no lines), signify a normally opened contact.
6. Condenser fan motors are thermally protected.
7. Three phase motors are protected under primary single phasing
conditions.
55