Carrier 50HJ004 Air Conditioner User Manual


 
43
Table 9—50HJ and 50he Fan Rpm at Motor Pulley Setting With Standard Motor*
UNIT
50HJ
50HE
MOTOR PULLEY TURNS OPEN
0
1
/
2
1 1
1
/
2
2 2
1
/
2
3 3
1
/
2
4 4
1
/
2
5 5
1
/
2
6
003
936 906 876 846 816 786 756 726 696 666 639
004
1044 1008 971 935 898 862 826 789 753 716 680
005
1185 1144 1102 1061 1019 978 936 895 853 812 770
006
1460 1425 1389 1354 1318 1283 1248 1212 1177 1141 1106 1070 1035
007
1585 1538 1492 1445 1399 1352 1305 1259 1212 1166 1119
*Approximate fan rpm sh own (standard motor/drive).
Table 10—50HJ, 50HE Fan Rpm at Motor Pulley Setting With High-Static Motor*
UNIT
MOTOR PULLEY TURNS OPEN
0
1
/
2
1 1
1
/
2
2 2
1
/
2
3 3
1
/
2
4 4
1
/
2
5 5
1
/
2
6
004
1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075
005
1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075
006
1685 1589 1557 1525 1493 1460 1428 1396 1364 1332 1300
007
1685 1589 1557 1525 1493 1460 1428 1396 1364 1332 1300
*Approximate fan rpm s hown (high-static motor/drive).
Table 11—Evaporator-Fan Motor Data — Standard Motor
UNIT
50HJ
50HE
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
UNIT VOLTAGE
MAXIMUM
AMP DRAW
003
ALL 0.58 580 2.0 75.0
004
Single 1.20 1000 208/230 4.9
Three 1.20 1000
208/230 4.9
460 2.2
575 2.2
005
Single 1.20 1000 208/230 4.9
Three 1.20 1000
208/230 4.9
460 2.2
575 2.2
006
Single 1.30 1650 208/230 9.2
Three 2.40 2120
208/230 6.7
460 3.0
575 3.0
007
Three 2.40 2120
208/230 6.7
460 3.0
575 3.0
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensuresthat the full horsepower and wattsrange of the motors can be utilized with confidence. Using the
fan motors up to the ratings shown in this table will not result in nuisance trippingor premature motor failure. Unit warranty will not be affected.
Table 12—Evaporator-Fan Motor Data — High-Static Motors
UNIT
50HJ
50HE
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
UNIT VOLTAGE
MAXIMUM
AMP DRAW
004
Three 2.40 2120
208/230 6.7
460 3.0
575 3.0
005
Three 2.40 2120
208/230 6.7
460 3.0
575 3.0
006
Three 2.90 2615
208/230 8.6
460 3.9
575 3.9
007
Three 2.90 2615
208/230 8.6
460 3.9
575 3.9
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensuresthat the full horsepower and wattsrange of the motors can be utilized with confidence. Using the
fan motors up to the ratings shown in this table will not result in nuisance trippingor premature motor failure. Unit warranty will not be affected.
50HE,HJ