Carrier 50HJ004 Air Conditioner User Manual


 
42
Table 8—CO
2
Sensor Standard Settings
SETTING EQUIPMENT OUTPUT
VENTILATION
RATE
(cfm/Person)
ANALOG
OUTPUT
CO
2
CONTROL RANGE
(ppm)
OPTIONAL
RELAY SETPOINT
(ppm)
RELAY
HYSTERESIS
(ppm)
1
Interface w/Standard
Building Control System
Proportional Any
0-10V
4-20 mA
0-2000 1000 50
2
Proportional Any
2-10V
7-20 mA
0-2000 1000 50
3
Exponential Any
0-10V
4-20 mA
0-2000 1100 50
4
Economizer
Proportional 15
0-10V
4-20 mA
0-1100 1100 50
5
Proportional 20
0-10V
4-20 mA
0- 900 900 50
6
Exponential 15
0-10V
4-20 mA
0-1100 1100 50
7
Exponential 20
0-10V
4-20 mA
0- 900 900 50
8
Health & Safety Proportional
0-10V
4-20 mA
0-9999 5000 500
9
Parking/Air Intakes/
LoadingDocks
Proportional
0-10V
4-20 mA
0-2000 700 50
LEGEND
ppm — PartsPer Million
6000
5000
4000
3000
2000
1000
0
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
DELTA P IN. WG
4&5ton
6 ton
3 ton
C06133
Fig. 46 --- Humidi--MiZert Adaptive Dehumidification System Static Pressure Drop (in. wg)
C06134
Fig. 47 --- Belt Drive Motor Mounting
C06041
Fig. 48 --- Evaporator--Fan Pulley Adjustment
50HE,HJ