Carrier 50HJ004 Air Conditioner User Manual


 
32
Table 5—PremierLinkSensor Usage
APPLICATION
OUTDOOR AIR
TEMPERATURE SENSOR
RETURN AIR
TEMPERATURE SENSOR
OUTDOOR AIR
ENTHALPY SENSOR
RETURN AIR
ENTHALPY SENSOR
Dry Bulb
Temperature with
Premier Link*
(PremierLink
requires 4-20 mA
Actuator)
Included ---
CRTEMPSN001A00
Differential Dry Bulb
Temperature with
Premier Link*
(PremierLink
requires 4-20 mA
Actuator)
Included ---
CRTEMPSN001A00
Required ---
33ZCT55SPT
or Eq uivalent
Single Enthalpy with
Premier Link*
(PremierLink
requires 4-20 mA
Actuator)
Included ---
Not Used
Required ---
HH57AC077
or Eq uivalent
Differential Enthalpy
with PremierLink*
(PremierLink
requires 4-20 mA
Actuator)
Included ---
Not Used
Required ---
HH57AC077
or Eq uivalent
Required ---
HH57AC078
or Eq uivalent
*PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and Outdoor Air Temperatur e sensor CRTEMPSN001A00
— Includedwith factory-installed PremierLink control; field-supplied and field-installed with field-installed PremierLink control.
NOTES:
1. CO
2
Sensors (Optional):
33ZCSENCO2— Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 — Aspirator box usedfor duct-mountedCO
2
room sensor.
33ZCT55CO2 — Space temperature and CO
2
room sensor with override.
33ZCT56CO2 — Space temperature and CO
2
room sensor with override and set point.
2. All units include the followingStandardSensors:
Outdoor-Air Sensor — 50HJ540569 — Opens at 67_F, closes at 52_F,not adjustable.
Mixed-Air S ensor — HH97AZ001 — (PremierLink control r equires Su pply Air Temperature sensor 33ZCSENSAT
and Outdoor Air Temperatu re Sensor CRTE MPSN001A00)
Compressor Lockout Sensor — 50HJ540570 — Opens at 35_F, closes at 50_F.
C06016
Fig. 22 --- PremierLink C ontroller
50HE,HJ