Carrier 50HJ004 Air Conditioner User Manual


 
27
Table 4 — Electrical Data--50HJ (cont)
UNIT
SIZE
NOMINAL
V ---PH--- Hz
IFM
TYPE
CONV
OUT-
LET
VOLTAGE
RANGE
COMPRESSOR(each) OUTDOORFAN
IFM
FLA
ELECTRIC HEAT POWERSUPPLY DISCONNECTSIZE
Min Max QTY RLA LRA QTY FLA
CRHEATER
--- ---A00 or
B00
Actual kW{ FLA MCA MOCP** FLA LRA
012
(10 ton)
575--- 3--- 60
STD
NO 518 632 2 6.3 50 2 0.6 3.3
18.7 25 20 133
18 17.0 16.4 24.6 25 23 133
019 34.0 32.7 45.0 50 41 133
018+019 51.0 49.1 53.2 60 60 133
YES 518 632 2 6.3 50 2 0.6 3.3
20.8 25 22 135
018 17.0 16.4 27.2 30 25 135
019 34.0 32.7 45.0 50 43 135
018+019 51.0 49.1 55.8 60 62 135
HS
NO 518 632 2 6.3 50 2 0.6 5.6
21.0 25 22 139
018 17.0 16.4 27.4 30 25 139
019 34.0 32.7 47.9 50 44 139
018+019 51.0 49.1 56.1 70 63 139
YES
518 632 2 6.3 50 2 0.6 5.6
23.1 25 24 141
018 17.0 16.4 30.1 35 27 141
019 34.0 32.7 47.9 60 46 141
018+019 51.0 49.1 58.7 70 65 141
HUMI-
DIMIZ-
ER
NO 518 632 2 6.3 50 2 0.7 7.4
21.2 25 23 146
018 17.0 16.4 27.8 30 26 146
019 34.0 32.7 48.3 50 44 146
018+019 51.0 49.1 56.5 70 63 146
YES 518 632 2 6.3 50 2 0.7 7.4
23.4 25 25 148
018 17.0 16.4 30.5 50 28 148
019 34.0 32.7 50.9 60 46 148
018+019 51.0 49.1 59.1 70 65 148
50HE,HJ