Burnham 8H Boiler User Manual


 
65
Green LED
Flash Code
(X + Y)
a
Indicates Next System Action Recommended Service Action
OFF No “Call for Heat” N/A None
Flash Fast
Startup - Flame sense
calibration
N/A None
Heartbeat Normal operation N/A None
2
5 minute Retry Delay-
Pilot ame not detected
during trial for ignition
Initiate new trial for ignition after
retry delay completed.
If system fails to light on next trial for
ignition check gas supply, pilot burner,
spark and ame sense wiring, ame rod
contamination or out of position, burner
ground connection.
3
Recycle- Flame failed
during run
Initiate new trial for ignition. Flash
code will remain through the ignition
trial until ame is proved.
If system fails to light on next trial
for ignition check gas supply, pilot
burner, ame sense wiring, ame rod
contamination, burner ground connection.
4
Flame sensed out of
sequence
If situation self corrects within 10
seconds, control returns to normal
sequence. If ame out of sequence
remains longer than 10 seconds,
control goes to Flash code 6+4 (see
below)
Check for pilot ame. Replace gas valve
if pilot ame present. If no pilot ame,
cycle “Call for Heat.” If error repeats,
replace control.
7
Flame sense leakage to
ground
Control remains in wait mode.
When the fault corrects, control
resumes normal operation after a
one minute delay.
Check ame sense lead wire for damage
or shorting. Check that ame rod is in
proper position. Check ame rod ceramic
for cracks, damage or tracking.
8
Low secondary voltage
supply- (below 15.5 Vac)
Control remains in wait mode.
When the fault corrects, control
resumes normal operation after one
minute delay.
Check transformer and AC line for proper
input voltage to the control. Check with
full system load on the transformer.
6 + 2
5 minute Retry Delay-
On every third retry on
same “Call for Heat”
Initiate new trial for ignition after
retry delay completed.
Check gas supply, pilot burner, spark
and ame sense wiring, ame rod
contamination or out of position, burner
ground connection.
6 + 3
On every 6th ame
failure during run on the
same “Call for Heat”
5 minute retry delay, then initiate
new trial for ignition.
Check gas supply, pilot burner, ame
sense wiring, contamination of ame rod,
burner ground connection.
6 + 4
Flame sensed out of
sequence- longer than
10 seconds
Control waits until ame is no
longer sensed and then goes to
soft lockout. Flash code continues.
Control auto resets from soft
lockout after one hour.
Check for pilot ame. Replace gas valve
if pilot ame present. If no pilot ame,
cycle “Call for Heat.” If error repeats,
replace control.
ON
Soft lockout due to error
detected during self
check sequences
Control auto resets from soft
lockout after one hour.
Reset by cycling “Call for Heat.” If error
repeats, replace the control
a
Flash Code Descriptions:
- Flash Fast: rapid blinking
- Heartbeat: Constant ½ second bright, ½ second dim cycles.
- A single ash code number signies that the LED ashes X times at 2Hz, remains off for two seconds, and then
repeats the sequence.
- X + Y ash codes signify that the LED ashes X times at 2Hz, remains off for two seconds, ashes Y times at
2 Hz, remains off for three seconds, and then repeats the sequence.
Honeywell EI Ignition Module Green LED Status Codes