Bryant 310JAV Furnace User Manual


 
Table 11Orifice Size* And Manifold Pressure For Gas Input Rate (Continued)
(Tabulated Data Based On 21,000 Btuh Per Burner, Derated 4 Percent For Each 1000 Ft Above Sea Level)
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
U.S.A. Only
9001
to
10,000
600 43 2.4 43 2.5 43 2.6 43 2.7
625 43 2.3 43 2.3 43 2.4 43 2.5
650 43 2.1 43 2.2 43 2.2 43 2.3
675 48 3.6 48 3.8 43 2.1 43 2.1
700 48 3.4 48 3.5 48 3.6 48 3.7
725 49 3.7 49 3.8 48 3.4 48 3.5
* Orifice numbers 43 are factory installed
41