Bosch Appliances ICP-CC404 Home Security System User Manual


 
ICP-CC404 | Installation Guide | 22.0 Programming Sheets
Bosch Security Systems, Inc. | 12/08 | F01U089401-02 87
Location
Function
Options/Notes
Default/
Programming Entry
185 to 264
User Codes
Refer to page 51
The fifth location in each user code is the authority level:
0 Arm/disarm
1 Arm only
2 Arm/disarm and open/close reports
3 Arm only and close reports
4 Arm/disarm and code required to isolate
6 Arm/disarm and open/close reports and code required to isolate
8 Master code and arm/disarm
10 Master code and arm/disarm and open/close reports
12 Master code and arm/disarm and code required to isolate
14 Master code and arm/disarm and code required to isolate and open/close reports
2 5 8 0 10 15 15 15 15 2
User #01 (185 to 189)
RF User #09 (225 to 229)
15 15 15 15 2 15 15 15 15 2
User #02 (190 to 194)
RF User #10 (230 to 234)
15 15 15 15 2 15 15 15 15 2
User #03 (195 to 199)
RF User #11 (235 to 239)
15 15 15 15 2 15 15 15 15 2
User #04 (200 to 204)
RF User #12 (240 to 244)
15 15 15 15 2 15 15 15 15 2
User #05 (205 to 209)
RF User #13 (245 to 249)
15 15 15 15 2 15 15 15 15 2
User #06 (210 to 214)
RF User #14 (250 to 254)
15 15 15 15 2 15 15 15 15 2
User #07 (215 to 219)
RF User #15 (255 to 259)
0 15 15 15 3 15 15 15 15 2
User #08 (220 to 224)
RF User #16 (260 to 264)
0
265
Day Alarm Zones
Refer to page 53
1 Zone 1
2 Zone 2
4 Zone 3
8 Zone 4
15
266
EOL Resistor Value
Refer to page 53
0 No EOL
1 1K
2 1K5
3 2K2
4 3K3
5 3K9
6 4K7
7 5K6
8 6K8
9 10K
10 12K
11 22K
12 Reserved
13 Reserved
14 Reserved
15 Split EOL (3K3/6K8) : Four
burglary zones and four 24-hr zones