Bosch Appliances ICP-CC404 Home Security System User Manual


 
ICP-CC404 | Installation Guide | 16.0 Programmable Outputs
68 Bosch Security Systems, Inc. | 12/08 | F01U089401-02
2,13 Radio Control Output 1 – Not in AWAY
Mode
This output operates when the [DOOR] button on the
four-channel hand-held transmitter is activated. The
output does not operate when the system is armed in
AWAY Mode.
2,14 Radio Control Output 2 – Not in AWAY
Mode
This output operates when the [AUX] button on the
four-channel hand-held transmitter is activated. The
output does not operate when the system is armed in
AWAY Mode.
2,15 Communications Failure after Three
Unsuccessful Calls
This output operates after the communication dialer
makes three unsuccessful calls to the base station
receiver. The output resets when all messages are sent
(that is, when the message buffer is empty or when all
possible attempts are made).
3,0 Communications Failure
This output operates after the communication dialer
makes all possible attempts to reach the base station
receiver. The output resets when the first kiss-off is
received. This output does not operate for domestic
formats.
3,1 Dialer Disabled
This output operates when the Dialer reporting
functions allowed Option 1 in Location 177 are not
selected (refer to Section 12.1 Dialer Options 1 on
page 50). The output resets when Option 1 is
selected.
3,2 Dialer Active
This output operates when the communication dialer
is online. The output resets when the communication
dialer releases the telephone line.
3,3 Ring Detect
This output operates when the control panel detects
an incoming call. The output resets when the ringing
stops or when the call is answered.
3,5 Mimic Zone 1
3,6 Mimic Zone 2
3,7 Mimic Zone 3
3,8 Mimic Zone 4
3,9 Mimic Zone 5
3,10 Mimic Zone 6
3,11 Mimic Zone 7
3,12 Mimic Zone 8
These output types mimic the zone inputs. The
output operates when the zone is unsealed and resets
when the zone is sealed. They operate regardless of
the selected zone type (for example, a zone
programmed as Not Used can still operate a mimic
output). This feature operates when the system is
armed or disarmed.
4,5 Global Chime
This output operates when any Chime zones are
activated. The output resets when the zone is
resealed. Refer to Section 14.3.1 Zone Types on page 55
for more information.
4,6 Zone Not Sealed
This output operates when a Burglary Zone is
unsealed. Chime zones do not operate this output.
4,7 Zone Not Sealed after Exit Time
This output operates at the end of Exit Time if a
Burglary Zone is unsealed. The output resets when all
zones are sealed or the system is disarmed. Chime
zones do not operate this output.
4,9 AC Mains 60 Hz or 50 Hz
This output is activated when the AC mains supply
frequency is 60 Hz. The output resets if the AC mains
supply returns to 50 Hz.
16.3 Output Polarity
There are fifteen different polarities. Each polarity is
designated by a number that you program into the
third location for the output.