Bosch Appliances ICP-CC404 Home Security System User Manual


 
ICP-CC404 | Installation Guide | 17.0 System Event Timers
72 Bosch Security Systems, Inc. | 12/08 | F01U089401-02
The Siren Sound Rate varies the frequency of the
siren tone slowest (0) and to fastest (15). The Siren
Sound Rate does not change the frequency of the fire
alarm tone.
17.11 Auto Arming Pre-Alert Timer
Program the Auto Arming Pre-Alert Timer into
Location 413 (increments of 5 min).
The default value for the Auto Arming Pre-Alert
Timer is 1 (5 min).
This location sets the time period during which the
control panel warns you it is automatically armed in
AWAY Mode. The codepad beeps once every second
until the Pre-Alert Timer expires: the system then
automatically arms itself in AWAY Mode. If you
want the system to automatically arm in STAY Mode
1, select Option 4 in Location 428 (refer to Section
18.5 Consumer Options 1 on page 75).
After the control panel automatically arms in AWAY
Mode or STAY Mode 1, Exit Time starts. If a valid
User Code is entered during the Pre-Alert Time, the
Auto Arming Time programmed in Locations 414 to
417 (refer to Section 17.12 Auto Arming Time) is
extended by 1 hour.
If you want a programmable output to operate during
the Auto Arming Pre-Alert Time, use Output Event
Type 0,5 Auto Arm Pre-Arming Alert Time (refer to
page 65).
17.12 Auto Arming Time
Program the Auto Arming Time in Locations 414 to
417 as described in Table 58.
The default value is midnight (0 0 0 0).
Table 58: Auto Arming Time Parameters
Location Parameter Default
414 Hour of day (tens digit) 0
415 Hour of day (units digit) 0
416 Minute of day (tens digit) 0
417 Minute of day (units digit) 0
These locations specify the time of the day that the
system automatically arms itself in AWAY Mode. Set
this time in 24-hour format (for example, program
10:30 PM as 2230). If you want the system to arm in
STAY Mode 1, select Option 4 in Location 428 (refer
to Section 18.5 Consumer Options 1 on page 75).
If forced arming is disabled for any zone, the
automatic arming feature operates regardless of
whether any zones are unsealed. Refer to Section
14.3.6 Zone Options 2 on page 58 for more information
on programming zones for forced arming.
User Code 16 is reported when this feature is used.
17.13 Auto Disarming Time
Program the Auto Disarming Time in Locations 418
to 421 as described in Table 59.
The default value is midnight (0 0 0 0).
Table 59: Auto Disarming Time Parameters
Location Parameter Default
418 Hour of day (tens digit) 0
419 Hour of day (units digit) 0
420 Minute of day (tens digit) 0
421 Minute of day (units digit) 0
These locations specify the time of day that the
system automatically disarms itself. Set this time in
24-hour format (for example, program 10:30 PM as
2230).
User Code 16 is reported when this feature is used.
17.14 Kiss-Off Wait Time
Program the Kiss-Off Wait Time into Location 422
(increments of 500 millisec).
The default value for the Kiss-Off Wait Time is 3
(1500 ms).
This location sets the time that the control panel waits
for acknowledgment before resending a report. This
timer applies only to the 4 + 2 Express Format.
17.15 System Time
Program the System Time in Locations 901 to 904 as
described in Table 60.
The default value is 0 0 0 0.
Table 60: System Time Parameters
Location Parameter Default
901 Hour of day (tens digit) 0
902 Hour of day (units digit) 0
903 Minute of day (tens digit) 0
904 Minute of day (units digit) 0
The ICP-CC404 Control Panel has a real-time
24-hour clock you must set during installation. Set
this time in 24-hour HHMM format (for example,
program 10:30 PM as 2230). You must reset the
System Time every time power is removed from the
system.
A Master Code holder can also set the System Date
and Time (refer to Section 6.2.7 Setting the Date and
Time on page 36).
17.16 System Date
Program the System Date in Locations 905 to 910 as
described in Table 61.
The default value is 01 January, 2001 (0 1 0 1 0 1).