A.O. Smith 2000 Boiler User Manual


 
61
To support the recommended Troubleshooting, the R7910 has an Alert File. Review the Alert history for possible trends that may have
been occurring prior to the actual Lockout.
Note Column: H= Hold message; L=Lockout message; H or L= either Hold or Lockout depending on Parameter Conguration.
CODE DESCRIPTION RECOMMENDED TROUBLESHOOTING OF
LOCKOUT CODES
NOTE
Safety Data Faults
1 Uncongured safety data 1. New Device, complete device conguration and
safety verication.
2. If fault repeats, replace module.
L
2 Waiting for safety data verication 1. Device in Conguration mode and safety
parameters need verication and a device needs
reset to complete verication.
2. Conguration ended without verication, re enter
conguration, verify safety parameters and reset
device to complete verication.
3. If fault repeats, replace module.
L
Internal Operation Errors
3 Internal fault: Hardware fault Internal Fault.
1. Reset Module.
2. If fault repeats, replace module.
H
4 Internal fault: Safety Relay key feedback error H
5 Internal fault: Unstable power (DCDC) output H
6 Internal fault: Invalid processor clock H
7 Internal fault: Safety relay drive error H
8 Internal fault: Zero crossing not detected H
9 Internal fault: Flame bias out of range H
10 Internal fault: Invalid Burner control state L
11 Internal fault: Invalid Burner control state ag L
12 Internal fault: Safety relay drive cap short H
13 Internal fault: PII shorted to ILK H or L
14 Internal fault: HFS shorted to LCI H or L
15 Internal fault: Safety relay test failed due to
feedback ON
L
16 Internal fault: Safety relay test failed due to safety
relay OFF
L
17 Internal fault: Safety relay test failed due to safety
relay not OFF
L
18 Internal fault: Safety relay test failed due to
feedback not ON
L
19 Internal fault: Safety RAM write L
20 Internal fault: Flame ripple and overow H
21 Internal fault: Flame number of sample mismatch H
22 Internal fault: Flame bias out of range H
23 Internal fault: Bias changed since heating cycle
starts
H
24 Internal fault: Spark voltage stuck low or high H
25 Internal fault: Spark voltage changed too much
during ame sensing time
H
26 Internal fault: Static ame ripple H
27 Internal fault: Flame rod shorted to ground
detected
H
28 Internal fault: A/D linearity test fails H
29 Internal fault: Flame bias cannot be set in range H
TROUBLESHOOTING
TABLE 24. TROUBLESHOOTING CODES