York 300 Air Conditioner User Manual


 
036-21410-001-A-0502
32 Unitary Products Group
TABLE 23: COOLING CAPACITIES FOR DJ300 AT 125°F
RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 125
CFM
WB
TEMP °F
GROSS
CAPACITY
1
(MBH)
INPUT
POWER
2
(kW)
GROSS SENSIBLE CAPACITY
1
(MBH)
(RETURN AIR DRY BULB TEMP. - (°F) )
86 83 80 77 74 71 68
7500
72
256.5 32.33 170.6 149.2 127.8 106.4 85.0 #N/A #N/A
67
256.1 32.35 224.5 203.1 181.8 160.4 139.0 117.6 96.2
62
248.4 31.25 248.4 230.7 209.3 187.9 166.5 145.2 123.8
57
230.3 31.16 230.3 226.9 205.5 184.1 162.7 141.3 120.0
8750
72
266.9 32.57 188.9 163.6 138.4 113.1 87.8 #N/A #N/A
67
266.3 32.60 247.2 222.0 196.7 171.4 146.2 120.9 95.6
62
258.4 31.48 258.4 249.5 226.7 201.4 176.1 150.9 125.6
57
239.7 31.39 239.7 237.9 222.6 197.3 172.1 146.8 121.5
10000
72
277.3 32.82 207.3 178.1 148.9 119.8 90.6 #N/A #N/A
67
276.5 32.84 270.0 240.8 211.7 182.5 153.3 124.2 95.0
62
268.3 31.71 268.3 268.3 244.1 214.9 185.7 156.6 127.4
57
249.0 31.63 249.0 249.0 239.7 210.6 181.4 152.3 123.1
11250
72
284.0 33.13 221.6 188.3 155.1 121.9 88.7 #N/A #N/A
67
283.2 33.15 280.7 253.7 220.5 187.3 154.1 120.8 87.6
62
274.8 32.01 274.8 274.8 254.2 221.0 187.8 154.6 121.4
57
255.0 31.92 255.0 255.0 249.7 216.5 183.3 150.1 116.9
12500
72
290.7 33.44 235.9 198.6 161.3 124.1 86.8 #N/A #N/A
67
289.8 33.46 289.8 266.6 229.3 192.0 154.8 117.5 80.3
62
281.3 32.32 281.3 281.3 264.4 227.1 189.9 152.6 115.3
57
261.0 32.22 261.0 261.0 259.7 222.4 185.2 147.9 110.7
1. The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro-
priate blower performance table for the kW of the supply air blower motor.
2. These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.