York 300 Air Conditioner User Manual


 
036-21410-001-A-0502
18 Unitary Products Group
TABLE 9: COOLING CAPACITIES FOR DJ210 AT 85°F
RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 85
CFM
WB
TEMP °F
GROSS
CAPACITY
1
(MBH)
INPUT
POWER
2
(kW)
GROSS SENSIBLE CAPACITY
1
(MBH)
(RETURN AIR DRY BULB TEMP. - (°F) )
86 83 80 77 74 71 68
6000
72
238.9 14.24 142.6 125.5 108.4 91.3 74.2 #N/A #N/A
67
221.2 13.83 178.6 161.5 144.4 127.3 110.2 93.1 76.0
62
207.4 13.57 207.4 192.8 175.7 158.5 141.4 124.3 107.2
57
197.6 13.52 197.6 195.7 178.6 161.4 144.3 127.2 110.1
6500
72
246.1 14.36 154.5 135.8 117.0 98.3 79.5 #N/A #N/A
67
227.9 13.95 193.5 174.7 156.0 137.2 118.4 99.7 80.9
62
213.7 13.69 213.7 206.4 189.7 170.9 152.2 133.4 114.6
57
203.6 13.64 203.6 202.6 192.8 174.1 155.3 136.5 117.8
7000
72
253.4 14.48 166.5 146.1 125.7 105.3 84.9 #N/A #N/A
67
234.6 14.06 208.3 187.9 167.5 147.1 126.7 106.3 85.9
62
220.0 13.80 220.0 220.0 203.7 183.3 162.9 142.5 122.1
57
209.6 13.75 209.6 209.6 207.1 186.7 166.2 145.8 125.4
7875
72
258.4 14.56 180.9 157.6 134.4 111.2 87.9 #N/A #N/A
67
239.3 14.14 225.6 202.4 179.1 155.9 132.6 109.4 86.1
62
224.4 13.88 224.4 224.4 216.2 193.0 169.7 146.5 123.2
57
213.8 13.82 213.8 213.8 212.5 189.2 166.0 142.8 119.5
8750
72
263.5 14.63 195.3 169.2 143.1 117.0 91.0 #N/A #N/A
67
243.9 14.21 242.9 216.8 190.7 164.7 138.6 112.5 86.4
62
228.7 13.95 228.7 228.7 228.7 202.6 176.6 150.5 124.4
57
217.9 13.90 217.9 217.9 217.9 191.8 165.8 139.7 113.6
1. The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro-
priate blower performance table for the kW of the supply air blower motor.
2. These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.