York 300 Air Conditioner User Manual


 
036-21410-001-A-0502
Unitary Products Group 21
TABLE 12: COOLING CAPACITIES FOR DJ210 AT 115°F
RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 115
CFM
WB
TEMP °F
GROSS
CAPACITY
1
(MBH)
INPUT
POWER
2
(kW)
GROSS SENSIBLE CAPACITY
1
(MBH)
(RETURN AIR DRY BULB TEMP. - (°F) )
86 83 80 77 74 71 68
6000
72
197.6 19.49 125.5 108.3 91.2 74.1 57.0 #N/A #N/A
67
183.1 19.04 162.2 145.1 128.0 110.9 93.8 76.7 59.6
62
176.3 18.92 176.3 160.2 143.1 126.0 108.9 91.8 74.7
57
162.8 18.55 162.8 162.8 145.7 128.6 111.5 94.4 77.3
6500
72
204.8 19.63 137.9 119.1 100.3 81.6 62.8 #N/A #N/A
67
189.9 19.18 178.3 159.5 140.8 122.0 103.3 84.5 65.8
62
182.8 19.06 182.8 174.8 157.4 138.6 119.9 101.1 82.4
57
168.8 18.69 168.8 168.8 160.3 141.5 122.8 104.0 85.2
7000
72
212.1 19.77 150.3 129.9 109.5 89.0 68.6 #N/A #N/A
67
196.6 19.32 194.4 174.0 153.6 133.2 112.7 92.3 71.9
62
189.3 19.20 189.3 189.3 171.7 151.3 130.9 110.5 90.0
57
174.8 18.82 174.8 174.8 174.8 154.4 134.0 113.6 93.2
7875
72
213.7 19.85 165.7 142.5 119.2 96.0 72.7 #N/A #N/A
67
198.1 19.40 197.0 186.8 167.3 144.0 120.8 97.5 74.3
62
190.7 19.28 190.7 190.7 181.9 158.6 135.4 112.1 88.9
57
176.1 18.90 176.1 176.1 176.1 152.9 129.6 106.4 83.1
8750
72
215.2 19.94 181.1 155.1 129.0 102.9 76.8 #N/A #N/A
67
199.5 19.48 199.5 199.5 181.0 154.9 128.8 102.7 76.6
62
192.1 19.36 192.1 192.1 192.1 166.0 139.9 113.8 87.8
57
177.4 18.98 177.4 177.4 177.4 151.3 125.2 99.1 73.1
1. The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro-
priate blower performance table for the kW of the supply air blower motor.
2. These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.