York 300 Air Conditioner User Manual


 
036-21410-001-A-0502
22 Unitary Products Group
TABLE 13: COOLING CAPACITIES FOR DJ210 AT 125°F
RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 125
CFM
WB
TEMP °F
GROSS
CAPACITY
1
(MBH)
INPUT
POWER
2
(kW)
GROSS SENSIBLE CAPACITY
1
(MBH)
(RETURN AIR DRY BULB TEMP. - (°F) )
86 83 80 77 74 71 68
6000
72
184.9 21.33 119.9 102.8 85.7 68.6 51.5 #N/A #N/A
67
171.1 20.87 156.9 139.8 122.7 105.6 88.5 71.4 54.3
62
165.7 20.84 165.7 149.9 132.7 115.6 98.5 81.4 64.3
57
151.2 20.30 151.2 151.2 136.2 119.1 102.0 84.9 67.8
6500
72
191.4 21.49 132.0 113.2 94.4 75.7 56.9 #N/A #N/A
67
177.1 21.03 172.7 154.0 135.2 116.5 97.7 79.0 60.2
62
171.5 21.00 171.5 163.6 146.3 127.5 108.8 90.0 71.3
57
156.5 20.46 156.5 156.5 150.1 131.4 112.6 93.8 75.1
7000
72
197.8 21.65 144.0 123.6 103.2 82.8 62.3 #N/A #N/A
67
183.1 21.19 183.1 168.1 147.7 127.3 106.9 86.5 66.1
62
177.3 21.16 177.3 177.3 159.8 139.4 119.0 98.6 78.2
57
161.8 20.61 161.8 161.8 161.8 143.6 123.2 102.8 82.4
7875
72
198.9 21.74 160.2 136.9 113.7 90.4 67.2 #N/A #N/A
67
184.1 21.27 184.1 180.2 162.6 139.4 116.2 92.9 69.7
62
178.2 21.24 178.2 178.2 169.5 146.3 123.0 99.8 76.5
57
162.6 20.69 162.6 162.6 162.6 140.5 117.3 94.0 70.8
8750
72
199.9 21.82 176.3 150.2 124.2 98.1 72.0 #N/A #N/A
67
185.1 21.35 185.1 185.1 177.6 151.5 125.4 99.3 73.2
62
179.2 21.32 179.2 179.2 179.2 153.1 127.0 100.9 74.8
57
163.5 20.77 163.5 163.5 163.5 137.4 111.3 85.2 59.2
1. The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro-
priate blower performance table for the kW of the supply air blower motor.
2. These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.