York 300 Air Conditioner User Manual


 
036-21410-001-A-0502
24 Unitary Products Group
TABLE 15: COOLING CAPACITIES FOR DJ240 AT 95°F
RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 95
CFM
WB
TEMP °F
GROSS
CAPACITY
1
(MBH)
INPUT
POWER
2
(kW)
GROSS SENSIBLE CAPACITY
1
(MBH)
(RETURN AIR DRY BULB TEMP. - (°F) )
86 83 80 77 74 71 68
6000
72
257.3 18.45 150.2 133.1 116.0 98.9 81.8 #N/A #N/A
67
237.3 17.83 192.3 175.1 158.0 140.9 123.8 106.7 89.6
62
215.2 17.64 215.2 200.8 183.7 166.6 149.5 132.4 115.3
57
221.2 17.98 221.2 213.2 196.1 179.0 161.8 144.7 127.6
7000
72
264.7 18.51 167.2 146.9 126.7 106.5 86.3 #N/A #N/A
67
244.2 17.89 213.1 192.9 172.7 152.4 132.2 112.0 91.8
62
221.5 17.70 221.5 214.3 200.7 180.5 160.3 140.0 119.8
57
227.6 18.04 227.6 223.6 214.2 194.0 173.8 153.5 133.3
8000
72
272.2 18.58 184.1 160.8 137.4 114.1 90.8 #N/A #N/A
67
251.0 17.95 233.9 210.6 187.3 164.0 140.6 117.3 94.0
62
227.7 17.76 227.7 227.7 217.7 194.4 171.0 147.7 124.4
57
234.0 18.10 234.0 234.0 232.3 209.0 185.7 162.4 139.0
8700
72
277.5 18.98 195.6 169.9 144.2 118.5 92.9 #N/A #N/A
67
256.0 18.33 247.4 222.2 196.5 170.8 145.2 119.5 93.8
62
232.2 18.14 232.2 232.2 227.2 201.5 175.8 150.1 124.5
57
238.6 18.50 238.6 238.6 237.7 212.1 186.4 160.7 135.0
9400
72
282.9 19.38 207.0 179.0 151.0 123.0 94.9 #N/A #N/A
67
260.9 18.72 260.9 233.7 205.7 177.7 149.7 121.7 93.6
62
236.6 18.53 236.6 236.6 236.6 208.6 180.6 152.6 124.6
57
243.2 18.89 243.2 243.2 243.2 215.1 187.1 159.1 131.1
1. The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro-
priate blower performance table for the kW of the supply air blower motor.
2. These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.