York 300 Air Conditioner User Manual


 
036-21410-001-A-0502
Unitary Products Group 23
TABLE 14: COOLING CAPACITIES FOR DJ240 AT 85°F
RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 85
CFM
WB
TEMP °F
GROSS
CAPACITY
1
(MBH)
INPUT
POWER
2
(kW)
GROSS SENSIBLE CAPACITY
1
(MBH)
(RETURN AIR DRY BULB TEMP. - (°F) )
86 83 80 77 74 71 68
6000
72
273.1 16.90 149.8 132.7 115.6 98.5 81.4 #N/A #N/A
67
248.6 16.43 197.6 180.5 163.4 146.3 129.1 112.0 94.9
62
231.2 16.44 227.9 210.8 193.7 176.6 159.5 142.4 125.3
57
216.6 15.98 216.6 210.2 193.1 176.0 158.9 141.8 124.7
7000
72
278.7 16.96 165.8 145.6 125.4 105.1 84.9 #N/A #N/A
67
253.8 16.49 217.5 197.3 177.1 156.9 136.7 116.5 96.2
62
236.0 16.50 234.4 225.8 210.0 189.8 169.6 149.4 129.2
57
221.1 16.04 221.1 217.9 209.3 189.1 168.9 148.7 128.5
8000
72
284.4 17.02 181.8 158.4 135.1 111.8 88.4 #N/A #N/A
67
259.0 16.55 237.5 214.2 190.9 167.5 144.2 120.9 97.6
62
240.8 16.56 240.8 240.8 226.3 203.0 179.7 156.4 133.0
57
225.6 16.10 225.6 225.6 225.6 202.3 178.9 155.6 132.3
8700
72
291.0 17.43 193.1 167.5 141.8 116.1 90.4 #N/A #N/A
67
265.0 16.95 251.7 226.0 200.3 174.7 149.0 123.3 97.6
62
246.4 16.96 246.4 246.4 237.6 211.9 186.2 160.5 134.9
57
230.8 16.49 230.8 230.8 230.8 205.2 179.5 153.8 128.1
9400
72
297.7 17.84 204.5 176.5 148.5 120.5 92.4 #N/A #N/A
67
271.0 17.35 265.8 237.8 209.8 181.8 153.7 125.7 97.7
62
252.0 17.36 252.0 252.0 248.8 220.7 192.7 164.7 136.7
57
236.1 16.88 236.1 236.1 236.1 208.1 180.1 152.0 124.0
1. The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro-
priate blower performance table for the kW of the supply air blower motor.
2. These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.