York 300 Air Conditioner User Manual


 
036-21410-001-A-0502
14 Unitary Products Group
TABLE 5: COOLING CAPACITIES FOR DJ180 AT 95°F
RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 95
CFM
WB
TEMP °F
GROSS
CAPACITY
1
(MBH)
INPUT
POWER
2
(kW)
GROSS SENSIBLE CAPACITY
1
(MBH)
(RETURN AIR DRY BULB TEMP. - (°F) )
86 83 80 77 74 71 68
4500
72
201.7 13.56 117.1 104.3 91.5 78.6 65.8 #N/A #N/A
67
184.2 13.27 147.0 134.2 121.4 108.5 95.7 82.9 70.0
62 172.1 13.01 172.1 159.9 147.1 134.3 121.4 108.6 95.8
57
173.0 12.92 173.0 161.7 148.8 136.0 123.2 110.3 97.5
5250
72
207.4 13.65 129.7 114.5 99.3 84.2 60.0 #N/A #N/A
67 189.4 13.36 162.1 147.0 131.8 116.6 101.5 86.3 71.1
62
177.0 13.11 177.0 160.9 159.7 144.6 129.4 114.2 99.1
57
177.9 13.01 177.9 172.2 161.6 146.5 131.3 116.1 101.0
6000
72
213.1 13.75 142.2 124.7 107.2 89.7 72.2 #N/A #N/A
67
194.6 13.45 177.2 159.7 142.2 124.7 107.2 89.7 72.2
62
181.8 13.20 181.8 181.8 172.4 154.9 137.4 119.9 102.4
57 182.8 13.10 182.8 182.8 174.4 156.9 139.4 121.9 104.4
6750
72
219.3 13.78 153.6 133.6 113.7 93.8 73.9 #N/A #N/A
67
200.2 13.49 190.7 170.8 150.9 130.9 111.0 91.1 71.2
62 187.1 13.23 187.1 187.1 182.4 162.4 152.5 122.6 102.7
57
188.1 13.13 188.1 188.1 183.9 164.0 144.0 124.1 104.2
7500
72
225.4 13.81 164.9 142.6 120.2 97.9 75.5 #N/A #N/A
67 205.8 13.52 204.2 181.9 159.5 137.2 114.8 92.4 70.1
62
192.3 13.26 192.3 192.3 192.3 170.0 147.6 125.3 102.9
57
193.4 13.16 193.4 193.4 193.4 171.0 148.7 126.3 104.0
1. The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro-
priate blower performance table for the kW of the supply air blower motor.
2. These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.