York 300 Air Conditioner User Manual


 
036-21410-001-A-0502
Unitary Products Group 25
TABLE 16: COOLING CAPACITIES FOR DJ240 AT 105°F
RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 105
CFM
WB
TEMP °F
GROSS
CAPACITY
1
(MBH)
INPUT
POWER
2
(kW)
GROSS SENSIBLE CAPACITY
1
(MBH)
(RETURN AIR DRY BULB TEMP. - (°F) )
86 83 80 77 74 71 68
6000
72
244.1 20.09 146.5 129.4 112.3 95.2 78.1 #N/A #N/A
67
225.3 19.63 186.7 169.6 152.5 135.4 118.3 101.2 84.1
62
202.7 19.37 202.7 194.9 177.7 160.6 143.5 126.4 109.3
57
211.7 19.63 211.7 205.7 188.6 171.5 154.4 137.3 120.2
7000
72
250.6 20.15 162.5 142.2 122.0 101.8 81.6 #N/A #N/A
67
231.3 19.69 206.2 185.9 165.7 145.5 125.3 105.1 84.9
62
208.1 19.43 208.1 204.2 193.1 172.9 152.7 132.5 112.3
57
217.3 19.70 217.3 214.3 204.9 184.7 164.5 144.3 124.1
8000
72
257.0 20.22 178.4 155.1 131.7 108.4 85.1 #N/A #N/A
67
237.3 19.76 225.6 202.3 178.9 155.6 132.3 109.0 85.6
62
213.5 19.50 213.5 213.5 208.5 185.2 161.9 138.5 115.2
57
222.9 19.77 222.9 222.9 221.3 197.9 174.6 151.3 128.0
8700
72
264.1 20.56 191.3 165.6 139.9 114.3 88.6 #N/A #N/A
67
243.8 20.09 238.0 215.7 190.0 164.4 138.7 113.0 87.3
62
219.4 19.83 219.4 219.4 216.9 191.2 165.5 139.8 114.2
57
229.0 20.10 229.0 229.0 228.2 202.5 176.9 151.2 125.5
9400
72
271.1 20.91 204.1 176.1 148.1 120.1 92.1 #N/A #N/A
67
250.3 20.43 250.3 229.2 201.1 173.1 145.1 117.1 89.1
62
225.2 20.16 225.2 225.2 225.2 197.2 169.2 141.1 113.1
57
235.2 20.43 235.2 235.2 235.2 207.1 179.1 151.1 123.1
1. The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro-
priate blower performance table for the kW of the supply air blower motor.
2. These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.