TABLE 22: COOLING CAPACITIES FOR DJ300 AT 115°F
RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 115
CFM
WB
TEMP °F
GROSS
CAPACITY
1
(MBH)
INPUT
POWER
2
(kW)
GROSS SENSIBLE CAPACITY
1
(MBH)
(RETURN AIR DRY BULB TEMP. - (°F) )
86 83 80 77 74 71 68
7500
72
279.1 30.03 177.6 156.2 134.8 113.4 92.0 #N/A #N/A
67
272.6 29.81 231.6 210.3 188.9 167.5 146.1 124.7 103.3
62
266.0 28.91 266.0 245.2 223.8 202.4 181.0 159.6 138.3
57
250.9 28.79 250.9 243.6 222.2 200.8 179.4 158.1 136.7
8750
72
286.9 30.20 195.1 169.8 144.6 119.3 94.0 #N/A #N/A
67
280.1 29.98 253.1 227.9 202.6 177.3 152.0 126.8 101.5
62
273.3 29.07 273.3 262.9 240.0 214.8 189.5 164.2 138.9
57
257.9 28.96 257.9 254.2 238.3 213.1 187.8 162.5 137.3
10000
72
294.6 30.38 212.7 183.5 154.4 125.2 96.0 #N/A #N/A
67
287.6 30.16 274.6 245.5 216.3 187.1 158.0 128.8 99.7
62
280.7 29.24 280.7 280.7 256.3 227.1 198.0 168.8 139.6
57
264.8 29.13 264.8 264.8 254.5 225.3 196.2 167.0 137.8
11250
72
301.4 30.66 227.3 194.1 160.9 127.7 94.5 #N/A #N/A
67
294.3 30.44 287.8 258.7 225.5 192.3 159.1 125.9 92.7
62
287.2 29.52 287.2 287.2 267.2 234.0 200.8 167.6 134.3
57
270.9 29.40 270.9 270.9 265.3 232.1 198.9 165.7 132.5
12500
72
308.2 30.95 242.0 204.8 167.5 130.2 93.0 #N/A #N/A
67
300.9 30.72 300.9 272.0 234.7 197.4 160.2 122.9 85.7
62
293.6 29.79 293.6 293.6 278.1 240.8 203.6 166.3 129.0
57
277.0 29.68 277.0 277.0 276.1 238.9 201.6 164.3 127.1
1. The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro-
priate blower performance table for the kW of the supply air blower motor.
2. These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.