Event Log and Status at MX4428
Issue 1.5 24 March 2006 Page 6-3
6.2 FAULT AND ALARM EVENT LOG
The table below lists examples of event log items which are produced at the MX4428 panel.
Circuit / point event logging must be enabled to see the events listed below. Zone events are
not shown.
Event on MXP Event Logged Event Logged on return to
normal
Database tx from F4000
to MXP
R
SP 1 DATABASE TX
START
RSP 1 DATABASE TX
COMPLETE
Point Alarm
CCT 1/1 ALARM
PNT 1/30 ALARM
CCT 1/1 ALARM CLR
PNT 1/30 ALARM CLR
Point Fault
CCT 1/1 FAULT
PNT 1/20 FAULT
PNT 1/20 FAULT CLR
CCT 1/1 NORMAL
Point Pre-Alarm
PNT 1/3 PRE-ALARM PNT 1/3 ALARM CLR
SNM800 wiring o/c or
s/c
RLY 1/1 FAULT
PNT 1/26 SUPERVISION
FAULT
PNT 1/26 NORMAL OFF
RLY 1/1 NORMAL
SNM800 Supply Fail
RLY 1/1 FAULT
PNT 1/26 LOAD SUPPLY
FAIL
PNT 1/26 NORMAL OFF
RLY 1/1 NORMAL
SNM800 / RIM800
checkback fail
RLY 1/1 FAULT
PNT 1/24 CONTROL CB
FAIL
P
NT 1/24 CONTROL CB NML
(RIM800)
P
NT 1/26 NORMAL ON (or OFF)
(SNM800)
RLY 1/1 NORMAL
DIM800 Supply Low
CCT 1/1 FAULT
PNT 1/25 FAULT
PNT 1/25 LOAD SUPPLY
FAIL
PNT 1/25 FAULT CLR
CCT 1/1 NORMAL
Point scan fail
PNT 1/22 NODE FAIL
CCT 1/1 FAULT
PNT 1/22 NODE FAIL CLR
CCT 1/1 NORMAL
Detector calibration fault
CCT 1/1 FAULT
PNT 1/2 FAULT
PNT 1/2 PARAMETER
ERROR
CCT 1/1 NORMAL
PNT 1/2 FAULT
Loop o/c
RSP 1 LOOP OPEN
CIRCUIT
RSP 1 LOOP OPEN CIRCUIT
CLEARED
Loop line A or B short or
overload
RSP 1 LOOP SHORT
CIRCUIT
RSP 1 LOOP SHORT CIRCUIT
CLEARED
Type Mismatch
PNT 1/1 POINT TYPE
MISMATCH
PNT 1/1 POINT TYPE OK
Foreign Device
PNT 1/3 FOREIGN DEVICE (note- re-logged after DP command)
System Test or autotest
- device not normal at
start
PNT 1/2 TEST START NOT NML
CCT 1/1 FAIL SELF TEST 3 1
System Test or autotest
- device alarm test fail
PNT 1/1 ALARM TEST FAIL
CCT 1/1 FAIL SELF TEST 3 1
Zone alarm test device
fail
PNT 1/1 ALARM TEST FAIL
Diagnostic Pollscan result -Correct point found
P1/22 LINE 1 OK LINE 2 OK LED OFF
TYPE OK
Diagnostics Pollscan result - point not found
P1/100 LINE 1 FAULT LINE 2 FAULT LED
OFF TYPE OK
Diagnostic Pollscan result -Type mismatch
P1/20 LINE 1 OK LINE 2 OK LED OFF
TYPE BAD
Note “Type Mismatch” means a different device type was found at an address, from the type
programmed in the panel configuration for that address. An example of this would be a
MIM800 found at an address that is configured to have an 814PH. Refer to section
3.1.1 for
details of some device substitutions that are accepted without generating a fault.