Tyco MX4428 Smoke Alarm User Manual


 
Document: LT0273 MX4428 MXP Engineering / Technical Manual
MXP Diagnostic Terminal
Issue 1.5 24 March 2006 Page 8-11
4 : Flash Information
1
Erasing, wait
Erase OK
1 : Erase Entire Flash (all unprotected blocks)
3 : Load MXR Binary File and Program into Flash
4 : Flash Information
3
FlashPgm : Waiting for load
0134d0 bytes
000000
001000
002000
003000
004000
005000
006000
007000
008000
009000
00a000
00b000
00c000
00d000
00e000
00f000
010000
011000
012000
013000
Loaded
Checksum is correct
Done, Switch MXP DIP switches normal,
remove FLASH WRITE ENABLE LINK and press reset
MXR Flash Programmer V1.11.
1 : Erase Entire Flash (all unprotected blocks)
3 : Load MXR Binary File and Program into Flash
4 : Flash Information
9. If the above does not happen, check that all the required files are present, check the DIP
switch settings and WRITE ENABLE link and try starting again from the beginning - exit
from the program MXPPROG.EXE or MXPPROG32.exe by typing <ESC> and restart it,
the press the MXP RESET button again. If there is still a problem obtain a fresh copy of
the files and try again. If the problem persists, note carefully exactly what is displayed on
the screen and contact Tyco Safety Products Christchurch.
10. Remove the WRITE ENABLE link, or insert it onto one pin only.
11. Reset the DIP switches to the original settings noted in step 2.
12. Press the reset button.