Tyco MX4428 Smoke Alarm User Manual


 
MX4428 MXP Engineering / Technical Manual Document: LT0273
Device Information and Programming
Page 3-2 24 March 2006 Issue 1.5
3.1 DEVICE TYPES
The MXP can communicate with a mix of up to 200 addressable devices, within limits
defined by loop size.
3.1.1 MX DEVICES
MX devices fall into three basic types:
(a) Sensors - Detectors (814PH, 814CH, 814I, 814H, VLC800)
(b) Ancillaries - Input (Monitor) (MIM800, MIM801, CIM800, DIM800)
- MCP (CP820, FP0838, FP0839)
- Output (Control) (RIM800, SNM800, LPS800)
(c) Bases - Standard Base (MUB, 5B)
- Short Circuit Isolator (5BI)
- Relay Base (814RB)
- Sounder Base (814SB, MkII Sounder Base)
In addition non-addressable smoke, thermal or flame detectors may be connected to the
MXP loop by means of the DIM800 Detector Input Module.
Code Description Input /
Output
Remote
LED
814PH Photoelectric Smoke + Heat Detector I/O Y
814CH Carbon Monoxide + Heat Detector I/O Y
814I Ionisation Smoke Detector I/O Y
814H Heat Detector I/O Y
VLC800 Vesda Aspirating smoke detector I/O Y
MIM800 Mini Input Module Input
MIM801 Mini Input Module normally closed
interrupt (FP0837)
Input
CP820 Manual Call Point Input
FP0838
FP0839
NZ Manual Call Point Input
CIM800 Contact Input Module Input
DIM800 Detector Input Module Input
RIM800 Relay Interface Module (unsupervised
load wiring)
Output
SNM800 Sounder Notification Module (relay
output with supervised load wiring)
Output
LPS800 Loop Powered Sounder Output
The devices above are addressed by the
801AP Service Tool
or by command from the diagnostics terminal of an MXP.