3.21 RIM800 RELAY INTERFACE MODULE
3.21.1 GENERAL
The RIM800 Relay Interface Module is suitable for relay outputs which require clean voltage
free contacts and no supervision. For example it can be used to signal states to other
systems (e.g. BMS or security systems), or to energise loads that do not need to be
supervised, e.g. Door Holders.
3.21.2 RIM800 SPECIFICATIONS
Dimensions: Height: 61mm Width: 84mm Depth: 25mm
Weight 100g
Line Connections L-, L+
Supply Voltage 20V – 40V
Supply Current Standby Current : 285uA (typical)
LED on : 2.8mA (typical)
Contact Rating 2A 30Vdc
0.6A 120Vac (not permitted by AS / NZS standards)
0.3A 240Vac (not permitted by AS / NZS standards)
3.21.3 RIM800 FIELD WIRING
The field wiring is shown in Figure 3.7.
RIM800 RELAY MODULE
TB1
TB2
L+ L+L- L-
NEXT
DEVICE
PREVIOUS
DEVICE
ANALOG LOOP
O+ O-
N/O COM N/C
PSU
Normally
Energised
Load
Normally
DeEnergised
Load
Make no connection to O+ and O- terminals
Figure 3.7 RIM800 Field Wiring