Issue 1.5 24 March 2006 Page 8-9
DP r Perform a “diagnostic poll” on responder r. This command initiates a
diagnostic poll, similar to that described in section
8.1.6.4. The results are
displayed automatically on the MXP but not the MX4428. To see the results
on the MX4428 use the DR command.
DR r Display the results from the last DP command on responder r. (Use this
command at least 30 seconds after a DP command.)
GH r Reset history of all points on responder r.
GT r Reset tracked values (clean air values) of all points on responder r.
RH r p Reset history of point p on responder r.
RT r p Reset tracked value (clean air value) of point p on responder r.
The above commands are described in more detail in the F4000 Programming manual.
The remaining commands on the DA menu may display returned values from the MXP, but
have no direct affect on the MXP.
8.1.9 MXP EVENT LOG
Some events at the MXP are logged to the diagnostic terminal regardless of whether any
points are selected for display or commands entered at the MXP. These events are
generally self explanatory, and include –
MXP Powering up (logs message and displays diagnostic help menu.)
MXP Major state change including Initial Powerup state, Sending Learn Information,
Acquiring Database, Normal Running.
System test and Autotest initiated from MX4428, and result thereof.
Diagnostic Pollscan initiated from MX4428.
Pollscan to “Learn” system configuration initiated from MX4428.