Table 37 - Marking category of the gas section in different countries
Table 38 - Gas burner data
Country FR CH+ES-GB-IE-PT IT NL BE LU-DE AT-DK-Fl-SE
Category II2E+3P II2H3P II2H3+ II2L3P I2E+ & I3P I2E & I3P I2H
Type of gas Pressure in mbar
G20 20 20 20 - 20 20 20
G25 25 - - 25 25 20 -
G31 37 37 37 30 37 50 -
Burner G350
Natural Gas G20 (20mbar) 34.02 MJ/m
3
(15°C-1013)
Gas Flow (15 C-1013 mbar) (m
3
/h)
Nominal rate 8.1
Reduced rate 8.13
Heating Capacity (kW)
Nominal rate 69.3
Reduced rate 69.1
Heating Rate
(kW)
Nominal rate 77
Reduced rate 76.8
Efficiency %
Nominal rate 90
Reduced rate 90
Smoke analysis
G20 - 20mbar
@ 400V-3-50Hz
CO % < 0.001%
Nox ppm 9 ppm
CO
2
%
9.7%
G350
YK* 155-175-200-225 1
Burner G350
Natural Gas G25 (20 ou 25 mbar) 29.30 MJ/m
3
(15°C-1013)
Gas Flow (15 C-1013 mbar) (m
3
/h)
Nominal rate 8.8
Reduced rate 8.21
Heating Capacity (kW)
Nominal rate 62.9
Reduced rate 59.5
Heating Rate (kW)
Nominal rate 71.5
Reduced rate 66.8
Efficiency %
Nominal rate 88
Reduced rate 89
Smoke analysis
G25 - 25mbar
@ 400V-3-50Hz
CO % < 0.001%
Nox ppm -
CO
2
%
7. 4%
Burner G350
Propane Gas G31 (30, 37ou 50 mbar) 88.00 MJ/m
3
(15 C-1013)
Gas Flow (15 C-1013 mbar) (m
3
/h)
Nominal rate 2.7
Reduced rate 2.56
Gas Flow (15 C-1013 mbar) (kg/h)
Nominal rate 5.1
Reduced rate 4.9
Heating Capacity (kW)
Nominal rate 57.5
Reduced rate 55.3
Heating Rate (kW)
Nominal rate 65.3
Reduced rate 62.6
Efficiency
%
Nominal rate 88
Reduced rate 88.3
Combustion Air Flow
(Avec E=25%)
(m
3
/h)
Nominal rate 98
Reduced rate 93
Smoke analysis
G31 - 37mbar
@ 400V-3-50Hz
CO % < 0.001%
Nox ppm -
CO
2
%
8.9%