Supply fan performances
Table 10 - YK 155 External static pressure
Standard drive
Oversized drive
External Static Pressure (Pa)
275 300 325 350 375 400 425 450 475 500
m
3
/h RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
6800 699 1. 4 7 719 1. 5 5 739 1.6 3 758 1. 7 1 777 1.7 9 795 1. 8 6 813 1. 9 4 830 2.01 847 2.09 863 2.16
7650 729 1. 8 2 749 1. 9 2 768 2.01 787 2.1 806 2.19 824 2.28 841 2.37 858 2.46 875 2.55
8500 764 2.25 782 2.35 800 2.45 818 2.55
9350
10200
External Static Pressure (Pa)
25 50 75 100 125 150 175 200 225 250
m
3
/h RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
6800 564 1 587 1.0 7 610 1. 15 633 1. 2 3 655 1. 3 1 677 1. 39
7650 560 1. 1 4 583 1. 2 3 605 1.3 1 627 1.3 9 648 1.4 8 669 1.5 6 690 1. 6 5 710 1.74
8500 559 1. 3 1 584 1. 4 1 606 1. 5 628 1. 6 649 1. 6 9 669 1. 7 8 689 1. 87 708 1. 9 7 727 2.06 74 6 2.16
9350 610 1. 7 2 633 1. 8 3 654 1. 9 4 675 2.04 694 2.14 713 2.24 732 2.34 750 2.45 767 2.55 785 2.65
10200 661 2.21 683 2.33 703 2.45 722 2.56