Trane RT-SVX19A-E4 Thermostat User Manual


 
Installation
RT-SVX19A-E414
CAUTION! Do not operate unit
without filters in place.
The maximum pressure drops
allowable on filters are:
EU2/G2: 120 Pa
EU4/G4: 150 Pa
Filter installation
To gain access to filters, remove the
supply fan access panel on
downflow units and the filter access
panel on the end for horizontal
units.
Each unit ships with 40 or 50 mm
thick filters. Number and size of
filters is determined by size and
configuration of the unit.
Table 5 - Filter arrangement
UNIT
EU2/G2 EU4/G4
Qty Size Qty Size
YKH/YKD 155
2 (508x508x50) 2 (498x498x40)
4 (508x635x50) 4 (500x625x50)
YKH/YKD 175
2 (508x508x50) 2 (498x498x40)
4 (508x635x50) 4 (500x625x50)
YKH 200 8 (508x635x50) 8 (500x625x50)
YKD 200
4 (508x508x50) 4 (498x498x40)
4 (508x635x50) 4 (500x625x50)
YKH 250 8 (508x635x50) 8 (500x625x50)
YKD 250
4 (508x508x50) 4 (498x498x40)
4 (508x635x50) 4 (500x625x50)
TKH/TKD 155
2 (508x508x50) 2 (498x498x40)
4 (508x635x50) 4 (500x625x50)
TKH/TKD 175
2 (508x508x50) 2 (498x498x40)
4 (508x635x50) 4 (500x625x50)
TKH 200 8 (508x635x50) 8 (500x625x50)
TKD 200
4 (508x508x50) 4 (498x498x40)
4 (508x635x50) 4 (500x625x50)
TKH 250 8 (508x635x50) 8 (500x625x50)
TKD 250
4 (508x508x50) 4 (498x498x40)
4 (508x635x50) 4 (500x625x50)
WKH/WKD 125
2 (508x508x50) 2 (498x498x40)
4 (508x635x50) 4 (500x625x50)
WKH/WKD 155
2 (508x508x50) 2 (498x498x40)
4 (508x635x50) 4 (500x625x50)
WKH 200 8 (508x635x50) 8 (500x625x50)
WKD 200
4 (508x508x50) 4 (498x498x40)
4 (508x635x50) 4 (500x625x50)